7×24 服务热线Sales hotline 400-151-0319 厂址Address:河北省邢台市南宫经济开发区Nangong EDZ, Xingtai, Hebei
首页Home/产品中心Products/LNG 气化调压站LNG vaporizing and regulating station
Complete station: tank, unloading, vaporising, metering

LNG 气化调压站LNG vaporizing and regulating station

从储罐、卸车增压、气化、调压、计量到 BOG 处理的整站交付,含土建接口与自控。Whole-station delivery from tank and unloading booster through vaporisation, regulation and BOG handling.

1000Nm³/h单列常见规模Typical per train
2×双列并联可扩展Dual train ready
整站设计—制造—安装Design to installation
LNG 气化调压站
01 / Overview

产品概述Product overview

整站与单撬的区别在于“接口变多”:储罐液位与压力、卸车增压、气化器并联切换、调压计量、加臭、BOG 回收、放散与消防,任何一处没对上,整套站就跑不顺。泰燃按站交付时先出工艺流程图与平面布置,再定设备清单,最后按图做撬——顺序反过来,现场必然改管。A station has many more interfaces than a skid; P&ID and layout come first, equipment list second, fabrication last.

以已交付的空军某飞行学院项目为例:2 套 1000 Nm³/h LNG 气化站加 2 套 1000 Nm³/h CNG 减压站,2025 年 4 月签约、12 月完成验收,站址在黑龙江五常拉林镇,冬季极端低温是设计的第一约束条件。这类项目的气化器规格不能按铭牌选,必须按当地最冷月平均温度折算后再留余量。Reference: Air Force flight academy — 2×1000 Nm³/h LNG stations plus 2×1000 Nm³/h CNG stations, signed April 2025, accepted December 2025 in Heilongjiang; cold-climate sizing dominated design.

02 / Structure

结构组成What is on the skid

01
LNG 储罐与增压:立式/卧式真空储罐、自增压或卸车增压器。Vacuum tank with self-pressurising or unloading booster.
02
气化单元:空温式并联 + 水浴式复热,按冬季工况定台数。Parallel ambient vaporizers plus water-bath trim.
03
调压计量单元:两级调压、流量计量、加臭。Two-stage regulation, metering, odorisation.
04
BOG 处理:BOG 回收或复温后并入出口。BOG recovery or reheat to outlet.
05
安全系统:可燃气体探测、超压放散、消防联锁。Gas detection, relief, fire interlock.
06
自控:PLC + 触摸屏,液位/压力/温度/流量集中显示与远传。PLC with central display and remote signals.
03 / Advantages

核心优势Why this design

  • 先出图后制造:P&ID 与平面布置确认后才下料,减少现场改管。P&ID first, fabrication second.
  • 冬季工况折算:气化器按最冷月温度选型,不按铭牌。Vaporisers sized to coldest month.
  • 整站一家交付:设备与 GC2 级管道安装同一主体,责任清晰。Equipment and GC2 piping from one supplier.
  • 可分期扩容:预留并联接口,二期加列不动一期管路。Parallel interfaces for phased expansion.
04 / Specification

技术参数Technical data

整站规模Station size500–5000 Nm³/h(单列/多列)500–5000 Nm³/h
储罐容积Tank按日用气量与备用量确定Sized to daily demand and reserve
进口压力Inlet0.6–0.8 MPa(储罐出口)0.6–0.8 MPa
出口压力Outlet10–15 kPa / 0.2–0.4 MPa10–15 kPa / 0.2–0.4 MPa
气化配置Vaporisation空温式并联 + 水浴式复热Ambient parallel + water-bath trim
安装资质InstallationGC2 级工业管道安装许可GC2 piping licence
控制ControlPLC 集中监控,支持远程上传PLC with remote upload

表中为该系列典型配置。项目流量、介质与进出口压力不同时按工况单独设计,参数以合同技术文件为准。Typical configuration; units are engineered per duty and the contract data sheet governs.

05 / Duty

适用工况Typical duties

城镇燃气门站与储配站City gate and storage stations工业园集中供气Industrial park central supply部队、院校等独立供气Institutional independent supply冬季保供与应急调峰Winter peak shaving
07 / Related

同类设备Related equipment

把你的工况发过来,我们出选型表Send your duty, we return a selection sheet

需要提供:介质、最大/最小流量、进口压力、出口压力、现场热源(电/热水/蒸汽)、安装场地条件。We need medium, min/max flow, inlet and outlet pressure, available heat source and site conditions.